Quick Jump
|
25kV Copper Conductor 90°C (UL) Rating
Conductor Shield – Non-Conducting Permashield®
Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping
Semi-Conducting Layer
Concentric Wires – One-third or Full Neutral
Jacket – Insulating Polyethylene (PE) with 3 Red
stripes, Semi-Conducting Available
|
Catalog Numbers
|
One-Third Neutral |
Catalog Number Suffix =
A3200
260 mil Insulation (100%)* |
Catalog Number Suffix =
C3200
320 mil Insulation (133%)* |
|
CATALOG
NO. PREFIX |
SIZE
(AWG/kcmil) |
No Of
Strands |
Copper
Neutral
Wires
(No#AWG) |
O.D. Over
Insulation
(Inches) |
O.D. Over
Jacket
(Inches) |
Cable
Weight
(lbs/kft) |
O.D. Over
Insulation
(Inches) |
O.D. Over
Jacket
(Inches) |
Cable
Weight
(lbs/kft) |
|
101C25- |
1 |
19 |
7 - #14 |
0.885 |
1.193 |
0.769 |
1.011 |
1.319 |
0.866 |
|
111C25- |
1/0 |
19 |
9 - #14 |
0.924 |
1.232 |
0.887 |
1.050 |
1.378 |
1.026 |
|
121C25- |
2/0 |
19 |
11 - #14 |
0.967 |
1.275 |
1.023 |
1.093 |
1.421 |
1.168 |
|
141C15- |
4/0 |
19 |
18 - #14 |
1.070 |
1.398 |
1.439 |
1.196 |
1.524 |
1.577 |
|
125C25- |
250 |
37 |
21 - #14 |
1.134 |
1.462 |
1.639 |
1.260 |
1.588 |
1.784 |
|
135C25- |
350 |
37 |
18 - #12 |
1.237 |
1.599 |
2.115 |
1.363 |
1.791 |
2.344 |
|
150C25- |
500 |
37 |
17 - #10 |
1.365 |
1.835 |
2.930 |
1.491 |
1.961 |
3.107 |
|
175C25- |
750 |
61 |
20 - #9 |
1.554 |
2.079 |
4.156 |
1.68 |
2.205 |
4.354 |
|
Full Neutral |
Catalog Number Suffix =
A1200
260 mil Insulation (100%)* |
Catalog Number Suffix =
C1200
320 mil Insulation (133%)* |
|
101C15- |
1 |
19 |
20 - #14 |
0.885 |
1.193 |
0.939 |
1.011 |
1.319 |
1.056 |
|
111C15- |
1/0 |
19 |
16 - #12 |
0.924 |
1.266 |
1.104 |
1.050 |
1.412 |
1.244 |
|
121C15- |
2/0 |
19 |
20 - #12 |
0.967 |
1.309 |
1.297 |
1.093 |
1.455 |
1.443 |
|
141C25- |
4/0 |
19 |
20 - #10 |
1.070 |
1.474 |
1.870 |
1.196 |
1.600 |
2.009 |
|
Five minute AC Final Test Voltages
260 mil Insulation Level: 52kV
320 mil Insulation Level: 64kV
|
|
|
 |
|