Quick Jump

25kV Copper Conductor 90°C (UL) Rating


Conductor Shield – Non-Conducting Permashield® Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping Semi-Conducting Layer
Concentric Wires – One-third or Full Neutral
Jacket – Insulating Polyethylene (PE) with 3 Red stripes, Semi-Conducting Available



Catalog Numbers



One-Third Neutral

Catalog Number Suffix = A3200

260 mil Insulation (100%)*

Catalog Number Suffix = C3200

320 mil Insulation (133%)*

CATALOG

NO.  PREFIX

SIZE

(AWG/kcmil)

No Of

Strands

Copper

Neutral

Wires

(No#AWG)

O.D. Over

Insulation

(Inches)

O.D. Over

Jacket

(Inches)

Cable

Weight

(lbs/kft)

O.D. Over

Insulation

(Inches)

O.D. Over

Jacket

(Inches)

Cable

Weight

(lbs/kft)

101C25-

1

19

7 - #14

0.885

1.193

0.769

1.011

1.319

0.866

111C25-

1/0

19

9 - #14

0.924

1.232

0.887

1.050

1.378

1.026

121C25-

2/0

19

11 - #14

0.967

1.275

1.023

1.093

1.421

1.168

141C15-

4/0

19

18 - #14

1.070

1.398

1.439

1.196

1.524

1.577

125C25-

250

37

21 - #14

1.134

1.462

1.639

1.260

1.588

1.784

135C25-

350

37

18 - #12

1.237

1.599

2.115

1.363

1.791

2.344

150C25-

500

37

17 - #10

1.365

1.835

2.930

1.491

1.961

3.107

175C25-

750

61

20 - #9

1.554

2.079

4.156

1.68

2.205

4.354

Full Neutral

Catalog Number Suffix = A1200

260 mil Insulation (100%)*

Catalog Number Suffix = C1200

320 mil Insulation (133%)*

101C15-

1

19

20 - #14

0.885

1.193

0.939

1.011

1.319

1.056

111C15-

1/0

19

16 - #12

0.924

1.266

1.104

1.050

1.412

1.244

121C15-

2/0

19

20 - #12

0.967

1.309

1.297

1.093

1.455

1.443

141C25-

4/0

19

20 - #10

1.070

1.474

1.870

1.196

1.600

2.009

 

 

 



Five minute AC Final Test Voltages
    260 mil Insulation Level: 52kV
    320 mil Insulation Level: 64kV