Quick Jump
|
25kV Aluminum Conductor 90°C (UL) Rating
Conductor Shield – Non-Conducting Permashield®
Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping
Semi-Conducting Layer
Concentric Wires – One-third or Full Neutral
Jacket – Insulating Polyethylene (PE) with 3 Red
stripes, Semi-Conducting Available
|
Catalog Numbers
|
One-Third Neutral |
Catalog Number Suffix =
A3200
260 mil Insulation (100%)* |
Catalog Number Suffix =
C3200
320 mil Insulation (133%)* |
|
CATALOG
NO. PREFIX |
SIZE
(AWG/kcmil) |
No Of
Strands |
Copper
Neutral
Wires
(No-#AWG) |
O.D. Over
Insulation
(Inches) |
O.D. Over
Jacket
(Inches) |
Cable
Weight
(lbs/kft) |
O.D. Over
Insulation
(Inches) |
O.D. Over
Jacket
(Inches) |
Cable
Weight
(lbs/kft) |
|
101S25- |
1 |
SOL |
6 - #14 |
0.861 |
1.169 |
0.570 |
0.987 |
1.295 |
0.687 |
|
101A25- |
1 |
19 |
6 - #14 |
0.885 |
1.193 |
0.585 |
1.011 |
1.319 |
0.705 |
|
111S25- |
1/0 |
SOL |
6 - #14 |
0.897 |
1.205 |
0.611 |
1.023 |
1.331 |
0.733 |
|
111A25- |
1/0 |
19 |
6 - #14 |
0.924 |
1.232 |
0.630 |
1.050 |
1.378 |
0.773 |
|
121S25- |
2/0 |
SOL |
7 - #14 |
0.937 |
1.245 |
0.675 |
1.063 |
1.391 |
0.819 |
|
121A25- |
2/0 |
19 |
7 - #14 |
0.967 |
1.275 |
0.696 |
1.093 |
1.421 |
0.844 |
|
141A25- |
4/0 |
19 |
11 - #14 |
1.070 |
1.398 |
0.904 |
1.196 |
1.524 |
1.046 |
|
125A25- |
250 |
37 |
13 - #14 |
1.134 |
1.462 |
1.008 |
1.260 |
1.588 |
1.158 |
|
135A25- |
350 |
37 |
18 - #14 |
1.237 |
1.565 |
1.234 |
1.363 |
1.757 |
1.467 |
|
150A25- |
500 |
37 |
16 - #12 |
1.365 |
1.793 |
1.633 |
1.491 |
1.919 |
1.815 |
|
175A25- |
750 |
61 |
24 - #12 |
1.554 |
2.012 |
2.215 |
1.680 |
2.138 |
2.420 |
|
190A25- |
1000 |
61 |
20 - #10 |
1.703 |
2.203 |
2.724 |
1.829 |
2.329 |
2.945 |
|
Full Neutral |
Catalog Number Suffix =
A1200
260 mil Insulation (100%)* |
Catalog Number Suffix =
C1200
320 mil Insulation (133%)* |
|
101S25- |
1 |
SOL |
13 - #14 |
0.861 |
1.169 |
0.661 |
0.987 |
1.295 |
0.778 |
|
101A25- |
1 |
19 |
13 - #14 |
0.885 |
1.193 |
0.676 |
1.011 |
1.319 |
0.796 |
|
111S25- |
1/0 |
SOL |
16 - #14 |
0.897 |
1.205 |
0.742 |
1.023 |
1.331 |
0.864 |
|
111A25- |
1/0 |
19 |
16 - #14 |
0.924 |
1.232 |
0.761 |
1.050 |
1.378 |
0.904 |
|
121S25- |
2/0 |
SOL |
20 - #14 |
0.937 |
1.245 |
0.845 |
1.063 |
1.391 |
0.989 |
|
121A25- |
2/0 |
19 |
20 - #14 |
0.967 |
1.275 |
0.866 |
1.093 |
1.421 |
1.014 |
|
141A25- |
4/0 |
19 |
20 - #12 |
1.070 |
1.432 |
1.178 |
1.196 |
1.558 |
1.321 |
|
Five minute AC Final Test Voltages
260 mil Insulation Level: 52kV
320 mil Insulation Level: 64kV
|
|
|
 |
|