Quick Jump

15kV Aluminum Conductor 90°C Rating


Conductor Shield – Non-Conducting Permashield® Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping Semi-Conducting Layer
Concentric Wires – One-third or Full Neutral
Jacket – Insulating Polyethylene (PE) with 3 Red stripes, Semi-Conducting Available



Catalog Numbers



One-Third Neutral

Catalog Number Suffix = J3200

175 mil Insulation (100%)*

Catalog Number Suffix = K3200

220 mil Insulation (133%)*

CATALOG

NO.  PREFIX

SIZE

(AWG/kcmil)

No Of

Strands

Copper

Neutral

Wires

(No-#AWG)

O.D. Over
Insulation

(Inches)

O.D. Over

Jacket

(Inches)

Cable

Weight

(lbs/ft)

O.D. Over
Insulation

(Inches)

O.D. Over

Jacket

(Inches)

Cable

Weight

(lbs/ft)

Minimum

Maximum

Minimum

Maximum

102S15-

2

SOL

6 - #14

0.610

0.695

0.960

0.397

0.700

0.790

1.055

0.466

102F15-

2

7

6 - #14

0.635

0.720

0.990

0.411

0.725

0.815

1.080

0.482

101S15-

1

SOL

6 - #14

0.645

0.725

0.955

0.427

0.735

0.820

1.085

0.498

101A15-

1

7

6 - #14

0.675

0.760

1.015

0.441

0.765

0.855

1.110

0.514

111S15-

1/0

SOL

6 - #14

0.680

0.760

1.030

0.464

0.770

0.855

1.120

0.537

111F15-

1/0

19

6 - #14

0.715

0.800

1.055

0.480

0.805

0.895

1.150

0.555

121S15-

2/0

SOL

7 - #14

0.720

0.800

1.070

0.522

0.810

0.895

1.160

0.598

121F15-

2/0

19

7 - #14

0.760

0.845

1.100

0.539

0.850

0.935

1.190

0.617

141F15-

4/0

19

11 - #14

0.865

0.950

1.200

0.711

0.955

1.045

1.295

0.798

125A15-

250

37

13 - #14

0.920

1.005

1.265

0.805

1.010

1.100

1.380

0.916

135A15-

350

37

18 - #14

1.025

1.110

1.390

1.032

1.115

1.200

1.480

1.134

150A15-

500

37

16 - #12

1.150

1.235

1.550

1.339

1.240

1.330

1.710

1.522

175A15-

750

61

24 - #12

1.340

1.425

1.805

1.916

1.430

1.520

1.900

2.048

190A15-

1000

61

20 - #10

1.485

1.575

2.025

2.439

1.575

1.670

2.120

2.585

Full Neutral

Catalog Number Suffix = J1200

175 mil Insulation (100%)*

Catalog Number Suffix = K1200

220 mil Insulation (133%)*

102S15-

2

SOL

10 - #14

0.610

0.695

0.960

0.449

0.700

0.790

1.055

0.518

102F15-

2

7

10 - #14

0.635

0.720

0.990

0.463

0.725

0.815

1.080

0.534

101S15-

1

SOL

13 - #14

0.645

0.725

0.995

0.518

0.735

0.820

1.085

0.589

101A15-

1

7

13 - #14

0.675

0.760

1.015

0.532

0.765

0.855

1.110

0.605

111S15-

1/0

SOL

16 - #14

0.680

0.760

1.030

0.595

0.770

0.855

1.120

0.668

111F15-

1/0

19

16 - #14

0.715

0.800

1.055

0.611

0.805

0.895

1.150

0.686

121S15-

2/0

SOL

20 - #14

0.720

0.800

1.070

0.692

0.810

0.895

1.160

0.768

121F15-

2/0

19

20 - #14

0.760

0.845

1.100

0.709

0.850

0.935

1.190

0.787

141F15-

4/0

19

20 - #12

0.865

0.950

1.235

0.985

0.955

1.045

1.330

1.073

                         


Five minute AC Final Test Voltages
    175 mil Insulation Level: 35kV
    220 mil Insulation Level: 44kV