Quick Jump

Power Cables > Type MV 105

5kV Shielded (SPS) 105°C Rating

Related Products

Medium Voltage

5kV 15kV 25kV 35kV PILC Network Replacement

High Voltage

46kV 69kV 115kV 138kV

Conductor – Copper or Aluminum
Conductor Shield – Non-Conducting Permashield® Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping
Semi-Conducting Layer
Shielding – 5 mil Copper Tape
Jacket – Polyvinyl Chloride (PVC)


Catalog Numbers


CATALOG NUMBER SUFFIX = C4400

115 mil Insulation (133%)

Catalog Number Prefix

Size

(AWG/kcmil)

Number of Strands

O.D. Over

Insulation

(inches)

Jacket

Cable

Weight

(lbs/kft)

Thickness

(mils)

O.D.

(inches)

106C05-

6

7

0.464

60

0.678

0.302

104C05-

4

7

0.511

60

0.725

0.372

102C05-

2

7

0.571

60

0.785

0.478

101C05-

1

19

0.599

60

0.813

0.545

111C05-

1/0

19

0.638

60

0.852

0.632

121C05-

2/0

19

0.681

80

0.939

0.776

141C05-

4/0

19

0.784

80

1.042

1.073

125X05-

250

37

0.816

80

1.074

1.214

135X05-

350

37

0.912

80

1.170

1.575

150X05-

500

37

1.032

80

1.306

2.210

175X05-

750

61

1.225

80

1.499

3.013

190C05-

1000

61

1.417

80

1.691

3.883

*192C05-

1250

91

1.621

110

1.977

4.991

*195C05-

1500

91

1.741

110

2.097

5.846

*197C05-

1750

127

1.857

110

2.213

6.704

*199C05-

2000

127

1.960

110

2.316

7.547


* For conductors larger than 1000 kcmil 140 mils of insulation is required.

Five minute AC Final Test Voltages
    115 mil Insulation Level: 23kV
    140 mil Insulation Level: 28kV