Quick Jump
|
15kV Shielded (SPS) 105°C Rating
Conductor – Copper or Aluminum
Conductor Shield – Non-Conducting Permashield®
Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping
Semi-Conducting Layer
Shielding – 5 mil Copper Tape
Jacket – Polyvinyl Chloride (PVC)
|
Catalog Numbers
|
|
Catalog Number Suffix =
A4400
175 mil Insulation (100%) |
|
|
Catalog Number Prefix |
Size
(AWG/
(kcmil) |
Number of Strands |
O.D. Over
Insulation
(inches) |
Jacket |
Cable
Weight
(lbs/kft) |
|
|
Thickness
(mils) |
O.D.
(inches) |
|
|
|
|
102C15- |
2 |
7 |
0.681 |
80 |
0.939 |
0.603 |
|
|
101C15- |
1 |
19 |
0.709 |
80 |
0.967 |
0.674 |
|
|
111C15- |
1/0 |
19 |
0.748 |
80 |
1.006 |
0.766 |
|
|
121C15- |
2/0 |
19 |
0.791 |
80 |
1.049 |
0.879 |
|
|
141C15- |
4/0 |
19 |
0.894 |
80 |
1.152 |
1.185 |
|
|
125X15- |
250 |
37 |
0.926 |
80 |
1.184 |
1.328 |
|
|
135X15- |
350 |
37 |
1.022 |
80 |
1.296 |
1.714 |
|
|
150X15- |
500 |
37 |
1.142 |
80 |
1.416 |
2.255 |
|
|
175X15- |
750 |
61 |
1.335 |
80 |
1.609 |
3.167 |
|
|
190C15- |
1000 |
61 |
1.527 |
110 |
1.883 |
4.195 |
|
|
*192C15- |
1250 |
91 |
- |
- |
- |
- |
|
|
*195C15- |
1500 |
91 |
- |
- |
- |
- |
|
|
*197C15- |
1750 |
127 |
- |
- |
- |
- |
|
|
*199C15- |
2000 |
127 |
- |
- |
- |
- |
|
|
|
Catalog Number Suffix =
C4400
220 mil Insulation (133%) |
|
|
Catalog Number Prefix |
Size
(AWG/
(kcmil) |
Number of Strands |
O.D. Over
Insulation
(inches) |
Jacket |
Cable
Weight
(lbs/kft) |
|
|
Thickness
(mils) |
O.D.
(inches) |
|
|
|
|
102C15- |
2 |
7 |
0.773 |
80 |
1.031 |
0.687 |
|
|
101C15- |
1 |
19 |
0.801 |
80 |
1.059 |
0.761 |
|
|
111C15- |
1/0 |
19 |
0.840 |
80 |
1.098 |
0.856 |
|
|
121C15- |
2/0 |
19 |
0.883 |
80 |
1.141 |
0.971 |
|
|
141C15- |
4/0 |
19 |
0.986 |
80 |
1.244 |
1.286 |
|
|
125X15- |
250 |
37 |
1.018 |
80 |
1.312 |
1.469 |
|
|
135X15- |
350 |
37 |
1.114 |
80 |
1.388 |
1.827 |
|
|
150X15- |
500 |
37 |
1.234 |
80 |
1.508 |
2.376 |
|
|
175X15- |
750 |
61 |
1.427 |
80 |
1.701 |
3.304 |
|
|
190C15- |
1000 |
61 |
1.619 |
110 |
1.975 |
4.354 |
|
|
*192C15- |
1250 |
91 |
1.777 |
110 |
2.133 |
5.276 |
|
|
*195C15- |
1500 |
91 |
1.897 |
110 |
2.253 |
6.147 |
|
|
*197C15- |
1750 |
127 |
2.013 |
110 |
2.369 |
7.021 |
|
|
*199C15- |
2000 |
127 |
2.116 |
110 |
2.472 |
7.877 |
|
|
* For conductors larger than 1000 kcmil a 133% insulation level (220 mil) is required.
Five minute AC Final Test Voltages
175 mil Insulation Level: 35kV
220 mil Insulation Level: 44kV
|
|
|
 |
|