Quick Jump

Power Cables > Compact Power Cable

15kV, 25kV, 35kV Shielded (SPS) 105°C Rating

Related Products

Medium Voltage

5kV 15kV 25kV 35kV PILC Network Replacement

High Voltage

46kV 69kV 115kV 138kV

For replacement of Paper-Insulated Lead Covered (PILC) cables

Conductor – Compact Copper
Conductor Shield – Non-Conducting Permashield® Stress Control Layer
Insulation – Reduced Wall Discharge Resistant EPR Insulation
Insulation Shield – Extruded Free Stripping Semi-Conducting Layer
Shielding – Flat Strap Copper Concentric Neutrals
Jacket – Polyethylene (PE)

Replacing PILC cable with Kerite Compact Power Cable cuts nearly 50% of costs. These cables consist of compact copper strand conductors (that provide an eight to ten percent diameter reduction over full round conductors), Kerite’s exclusive Permashield® and EPR insulation system extruded to exacting tolerances, a free-stripping insulation shield, flat strap concentric neutrals and a jacket. During installation, Kerite cable terminates and splices faster than other solid dielectric cables plus providing substantial savings compared to PILC lead wipes, splices and terminations. Like all Kerite cable, our PILC replacement cables also offer excellent reliability and a proven track record.
 

Summary of Benefits

PILC Cables

Kerite Compact Power Cables

·         Lead and Oil Used in Manufacture

·         Labor Intensive

·         High Skill Level Required

·         Materials (Lead Wipe, Lead Pot)

·         Installation (Heavy Limit Pulls)

·         Environmental Issues

·         No Lead and No Oil Used

·         Labor Savings

·         Standard Lineperson Skills Required

·         Materials (No Lead Sleeve Required)

·         30% Lighter Cables (Longer, Easier Pulls)

 



Catalog Numbers


Catalog Number Suffix = IH100

Voltage and

Insulation System

Catalog

Number

Prefix

Size

(kcmil)

Flat Straps

(No.-AWG)

1/C

3-1/C

O.D.

(inches)

Cable Weight

(lbs/kft)

O.D.

(inches)

Cable Weight

(lbs/kft)

15kV

140 mil Insulation

135X15-

350

8 - #14

1.166

1.521

2.512

4.700

150X15-

500

11 - #14

1.286

2.073

2.771

6.406

175X15-

750

16 - #14

1.469

2.997

3.165

9.261

190X15-

1000

22 - #14

1.621

3.915

3.493

12.097

25kV

210 mil Insulation

 

135X25-

350

8 - #14

1.326

1.677

2.857

5.182

150X25-

500

11 - #14

1.446

2.246

3.116

6.940

175X25-

750

16 - #14

1.629

3.194

3.510

9.869

190X25-

1000

22 - #14

1.781

4.133

3.838

12.771

35kV

278 mil Insulation

 

135X25-

350

8 - #14

1.442

1.803

3.107

5.571

150X25-

500

11 - #14

1.562

2.385

3.366

7.370

175X25-

750

16 - #14

1.745

3.352

3.760

10.358

190X25-

1000

22 - #14

1.897

4.304

4.087

13.299