Quick Jump

Power Cables > High Voltage Cable

46kV Shielded (SPS) 90°C Rating

Related Products

Medium Voltage

5kV 15kV 25kV 35kV PILC Network Replacement

High Voltage

46kV 69kV 115kV 138kV

Conductor – Copper Strand
Conductor Shield – Non-Conducting Permashield® Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Thermosetting Semi-Conducting Semi-Conducting Layer
Shielding – Flat Strap Copper Concentric Neutrals
Jacket – Polyethylene (PE)



Catalog Numbers


Catalog Number Suffix = JH100

445 mil Insulation

 

Catalog Number Prefix

Size

(AWG/kcmil)

Number of Strands

O.D. Over

Insulation

(inches)

Jacket

Cable

Weight

(lbs/kft)

Thickness

(mils)

O.D.

(inches)

 

141C46-

4/0

19

1.460

80

1.788

1.662

 

125C46-

250

37

1.524

80

1.868

1.788

 

135C46-

350

37

1.627

80

1.971

1.994

 

150C46-

500

37

1.755

80

2.099

2.279

 

175C46-

750

61

1.944

80

2.288

2.724

 

190C46-

1000

61

2.093

80

2.437

3.122

 

192C46-

1250

91

2.251

80

2.595

3.548

 

195C46-

1500

91

2.371

80

2.715

3.917

 

197C46-

1750

127

2.487

80

2.831

4.270

 

199C46-

2000

127

2.590

80

2.934

4.620

 

 


Cable shield (15 #12 AWG wires) designed to carry 26kA for 6 cycles or 22kA for 8 cycles or 20kA for 10 cycles. Consult factory for custom shield designs.

Five minute AC Final Test Voltage: 89kV