Quick Jump
|
138kV Shielded (SPS) 90°C Rating
Conductor – Copper Strand
Conductor Shield – Non-Conducting Permashield®
Stress Control Layer
Insulation – Discharge Resistant EPR Insulation
Insulation Shield – Thermosetting Semi-Conducting
Semi-Conducting Layer
Shielding – Flat Strap Copper Concentric Neutrals
Jacket – Polyethylene (PE)
|
Catalog Numbers
|
Catalog Number
Suffix = JH100
850 mil
Insulation |
|
|
Catalog Number
Prefix |
Size
(AWG/kcmil) |
Number of Strands |
O.D. Over
Insulation
(inches) |
Jacket |
Cable
Weight
(lbs/kft) |
|
|
Thickness
(mils) |
O.D.
(inches) |
|
|
|
|
150C98- |
500 |
37 |
2.579 |
140 |
3.059 |
5.221 |
|
|
175C98- |
750 |
61 |
2.768 |
140 |
3.248 |
6.342 |
|
|
190C98- |
1000 |
61 |
2.917 |
140 |
3.397 |
7.384 |
|
|
192C98- |
1250 |
91 |
3.075 |
140 |
3.555 |
8.463 |
|
|
195C98- |
1500 |
91 |
3.195 |
140 |
3.675 |
9.455 |
|
|
197C98- |
1750 |
127 |
3.311 |
140 |
3.791 |
10.444 |
|
|
199C98- |
2000 |
127 |
3.414 |
140 |
3.894 |
11.405 |
|
|
Cable shield (15 #12 AWG Wires) designed to carry 26kA for 6 cycles = 22kA for 8 cycles = 20kA for 10 cycles.
Consult factory for custom shield designs.
AC Final Testing Voltage – 140kV for Thirty Minutes
|
|
|
 |
|