UNDERGROUND DISTRIBUTION CABLE (URD,UD) CONCENTRIC NEUTRAL
35kV COPPER - 90°C Rating (UL)

CONDUCTOR - Solid or Class "B" Strand
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION
- Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
CONCENTRICS - Neutrals as Specified Below
JACKET
-
50 mil Over Concentric Wire, Insulating LLDPE W/3 Red Stripes, Semiconducting Available


FULL NEUTRAL


  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX Single Phase
Single Conductor
11200 31200  
345 Mil Insulation (100%)* 420 Mil Insulation (133%)* Ampacity**
  Copper O.D. O.D.   O.D. O.D.    
CATALOG Size No. Neutral Over Over Cable Over Over Cable
NO. (AWG/ of Wires Insul. Jacket Weight Insul. Jacket Weight Direct Nonmetallic
PREFIX kcmil) Str. (No. - AWG) (Inches) (Inches) (lbs./kft) (Inches) (Inches) (lbs./kft) Burial Conduit
 
111C35- 1/0 19 25-#14 1.15 1.48 1406 1.32 1.65 1614 295 215
121C35- 2/0 19 20-#12 1.20 1.56 1645 1.36 1.72 1863 335 250
131C35- 3/0 19 25-#12 1.25 1.61 1891 1.41 1.77 2116 375 285
141C35- 4/0 19 20-#10 1.30 1.71 2248 1.47 1.87 2485 420 325
125C35- 250 37 25-#10 1.36 1.76 2568 1.53 1.93 2813 465 360

UNDERGROUND DISTRIBUTION CABLE (URD,UD) CONCENTRIC NEUTRAL
35kV COPPER - 90°C Rating (UL)

CONDUCTOR - Solid or Class "B" Strand
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION
- Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
CONCENTRICS - Neutrals as Specified Below
JACKET
-
50 mil Over Concentric Wire, Insulating LLDPE W/3 Red Stripes, Semiconducting Available

ONE-THIRD NEUTRAL
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX Three Phase
3 - 1/C Cables
Paralleled or
Triplexed
13200 33200
345 Mil Insulation (100%)* 420 Mil Insulation (133%)*  Ampacity**
  Copper O.D. O.D.   O.D. O.D.    
CATALOG Size No. Neutral Over Over Cable Over Over Cable
NO. (AWG/ of Wires Insul. Jacket Weight Insul. Jacket Weight Direct Nonmetallic
PREFIX kcmil) Str. (No. - AWG) (Inches) (Inches) (lbs./kft) (Inches) (Inches) (lbs./kft) Burial Conduit
 
111C35- 1/0 19 9-#14 1.15 1.48 1219 1.32 1.65 1427 235 220
121C35- 2/0 19 11-#14 1.20 1.52 1367 1.36 1.69 1582 265 250
131C35- 3/0 19 14-#14 1.25 1.57 1554 1.41 1.74 1775 295 280
141C35- 4/0 19 18-#14 1.30 1.63 1786 1.47 1.80 2015 335 320
125C35- 250 37 21-#14 1.36 1.69 1991 1.53 1.85 2228 365 355
135C35- 350 37 29-#14 1.46 1.79 2485 1.63 1.99 2779 430 420
150C35- 500 37 26-#12 1.59 1.98 3300 1.76 2.15 3577 505 500
175C35- 750 61 25-#10 1.78 2.21 4570 1.95 2.38 4878 595 595

Note:
The diameters and weights shown are approximate and subject to normal manufacturing tolerances.
* Approved for use on 15kV REA system. 
** Ampacity assumes:
1) Earth RHO 90°C - cm/Watt 4) 75% load factor
2) Earth ambient temperature 20°C 5) Average 36 inch burial depth
3) Average earth interface temperature limited to 45°C 6) Sheath losses included

 

Home | Index | Terms | www.kerite.com
Copyright © 2000 Kerite. All rights reserved

The Kerite Company
Phone: 203.888.2591 / 800.777.7483
Fax: 203.888.1987

Design by Innovative Systems

Home Index Terms and conditions www.kerite.com