UNDERGROUND DISTRIBUTION CABLE (URD,UD) CONCENTRIC NEUTRAL
25kV COPPER - 90°C Rating (UL)

CONDUCTOR
- Solid or Class "B" Strand
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION
- Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
CONCENTRICS - Neutrals as Specified Below
JACKET
-
50 mil Over Concentric Wire, Insulating LLDPE W/3 Red Stripes, Semiconducting Available


FULL NEUTRAL

  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX Single Phase
Single Conductor
11200 31200  
250 Mil Insulation (100%)* 320 Mil Insulation (133%)* Ampacity**
  Copper O.D. O.D.   O.D. O.D.    
CATALOG Size No. Neutral Over Over Cable Over Over Cable
NO. (AWG/ of Wires Insul. Jacket Weight Insul. Jacket Weight Direct Nonmetallic
PREFIX kcmil) Str. (No. - AWG) (Inches) (Inches) (lbs./kft) (Inches) (Inches) (lbs./kft) Burial Conduit
 
101C15- 1 19 20-#14 0.93 1.23 1038 1.06 1.36 1176 255 185
111C15- 1/0 19 25-#14 0.97 1.27 1192 1.10 1.42 1355 285 210
121C15- 2/0 19 20-#14 1.01 1.35 1420 1.14 1.50 1591 320 240
131C15- 3/0 19 25-#14 1.06 1.42 1678 1.19 1.55 1836 360 275
141C15- 4/0 19 20-#14 1.12 1.52 2022 1.25 1.65 2190 405 320
125C15- 250 37 25-#14 1.17 1.58 2335 1.30 1.71 2509 445 355

UNDERGROUND DISTRIBUTION CABLE (URD,UD) CONCENTRIC NEUTRAL
25kV COPPER - 90°C Rating (UL)

CONDUCTOR - Solid or Class "B" Strand
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION
- Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
CONCENTRICS - Neutrals as Specified Below
JACKET
-
50 mil Over Concentric Wire, Insulating LLDPE W/3 Red Stripes, Semiconducting Available

ONE-THIRD NEUTRAL
 
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX Three Phase
3 - 1/C Cables
Paralleled or
Triplexed
13200 33200
175 Mil Insulation (100%)* 220 Mil Insulation (133%)*  Ampacity**
  Copper O.D. O.D.   O.D. O.D.    
CATALOG Size No. Neutral Over Over Cable Over Over Cable
NO. (AWG/ of Wires Insul. Jacket Weight Insul. Jacket Weight Direct Nonmetallic
PREFIX kcmil) Str. (No. - AWG) (Inches) (Inches) (lbs./kft) (Inches) (Inches) (lbs./kft) Burial Conduit
 
101C25- 1 19 7-#14 0.93 1.23 886 1.06 1.36 1024 200 190
111C25- 1/0 19 9-#14 0.97 1.27 1005 1.10 1.42 1168 225 215
121C25- 2/0 19 11-#14 1.01 1.32 1146 1.14 1.47 1315 255 245
131C25- 4/0 19 14-#14 1.06 1.39 1346 1.19 1.52 1501 290 275
141C25- 4/0 19 18-#14 1.12 1.44 1570 1.25 1.57 1731 325 310
125C25- 250 37 21-#14 1.17 1.50 1767 1.30 1.63 1934 355 340
135C25- 350 37 29-#14 1.28 1.60 2246 1.41 1.73 2425 420 405
150C25- 500 37 26-#12 1.41 1.77 2996 1.54 1.90 3193 490 485
175C25- 750 61 25-#10 1.60 2.03 4273 1.73 2.16 4498 575 565

Note:
The diameters and weights shown are approximate and subject to normal manufacturing tolerances.
* Approved for use on 15kV REA system. 
** Ampacity assumes:
1) Earth RHO 90°C - cm/Watt 4) 75% load factor
2) Earth ambient temperature 20°C 5) Average 36 inch burial depth
3) Average earth interface temperature limited to 45°C 6) Sheath losses included

 

Home | Index | Terms | www.kerite.com
Copyright © 2000 Kerite. All rights reserved

The Kerite Company
Phone: 203.888.2591 / 800.777.7483
Fax: 203.888.1987

Design by Innovative Systems

Home Index Terms and conditions www.kerite.com