SHEATH LOSSES
T
he common practice of grounding cable shields in three phase systems at multiple locations results in induced voltages and circulating currents depending on the load currents and shield impedance.

With individually jacketed cables these currents can be eliminated by interrupting the shield and grounding each section at only one point. When using single point grounding, it is recommended that the voltage rise at the opposite end from ground of each section be limited to approximately 120 volts, under normal operating conditions. Circulating shield currents can also be reduced by cross bonding the shields to cancel out the induced voltages that generate these currents. (For more information on shield currents and cross bonding, refer to IEEE Standard 575).

VOLTAGE RISE IN OPEN SHEATHS
Eliminating the problem of circulating sheath currents by operating the circuit with grounding at one end results in a voltage being induced in the sheath. This voltage rise is proportional to distance from the ground point and the phase current. As covered under sheath losses the voltage rise should be limited to approximately 120 volts under normal operating conditions.

The following equation may be used for approximating the voltage rise on an open circuited sheath.

Where:
Vs = Voltage rise in open sheath (volts/1,000ft.)
Dm = Geometric mean distance between cables (inches)
Ds = Diameter of the shielding tape (inches)
lc = Current in the phase conductor (amps)

Note: Ds (the diameter of the shielding tape) can be arrived at by adding the value given in the table below to the diameter over the insulation or outer Permashield.

Diameter
Over the
Insulation (Inches)
 
Single
Permashield
Cables
Double and 
Triple
Permashield Cables
up to 1.000  0.065  0.013
1.001 to 1.500 0.085  0.013
1.501 and up 0.115 0.013


1 Cable per duct, equilateral spacing Dm = S.
For 3-1/C or 3/C twisted in one duct. Dm = cable O.D.

For flat spaced configuration
Dm = 1.26S

For rectangular configuration
Dm = 1.12S

The constants below can be used with the following formula to calculate the voltage rise in the sheath of 15kV, 25kV, and 35kV cables:

Where:
Vs = K x lc x 10-3        Volts/1,000 feet
 Vs = Voltage rise in open sheath (Volts/1,000 ft.)
K = Constant from table below
lc = Phase Current (Amperes)

CONSTANTS FOR USE IN CALCULATING VOLTAGE RISE ON OPEN
CIRCUITED SHIELDS
   15kV
Cable Configuration
 25kV
Cable Configuration
 35kV
Cable Configuration
 

Conductor
Size
(AWG/kcmil)

                 
A B C A B C A B C
2 23 77 74 -- -- -- -- -- --
1 23 76 73 22 71 68 -- -- --
1/0 23 75 72 22 70 67 21 66 63
2/0 22 73 71 21 69 66 21 65 62
3/0 22 72 69 21 68 65 21 64 61
4/0 22 72 68 21 67 64 20 63 60
250 21 69 67 21 65 63 20 62 59
350 21 67 64 21 64 61 20 60 58
500 21 65 62 20 61 59 20 58 56
750 21 61 58 20 58 55 20 56 53
1000 21 59 56 20 56 53 20 54 51

For Configuration: 
    A: S = Cable O.D.
B: S = 8 Inches
C: S = 8 Inches

Example: One circuit of three single 500 kcmil, 15kV cables twisted, installed in a single duct carrying 495 amps.

K =21
Vs = 21 x 495 x 10-3
Vs = 10.4 Volts/1,000 feet

 

Home | Index | Terms | www.kerite.com
Copyright © 2000 Kerite. All rights reserved

The Kerite Company
Phone: 203.888.2591 / 800.777.7483
Fax: 203.888.1987

Design by Innovative Systems

Home Index Terms and conditions www.kerite.com