MINIMUM BENDING RADIUS

Installed Cable
The minimum bending radius for training/positioning should not be less than the figure determined from the table below.

Shielded Cable & Interlocked Armor Cable
All Voltages

-------------------------------------------------------------

The Greater Of:
12 x Single Conductor Outside Diameter
7 x Multi-Conductor Assembled Outside Diameter

Non-Shielded Cable
Single and Multiple Conductor-All voltages

  600V 2kV 5kV 8 kV
   
Through 500 kcmil 3 3 4

6 x Outside
Diameter

       
   
600-1750 kcmil 4 4 5

7 x Outside
Diameter

       
   
2000 kcmil and above 5 5 6

8 x Outside
Diameter

       

During Installation
Cable should not be pulled with a radius less than that determined for the installed cable. Due to limitation of side bearing pressure, it is recommended that larger radius bends be used.

 

 