MINIMUM
BENDING RADIUS
Installed
Cable
The
minimum bending radius for training/positioning should not be less
than the figure determined from the table below.
|
Shielded
Cable & Interlocked Armor Cable
All Voltages
|
| ------------------------------------------------------------- |
|
The Greater
Of:
12 x Single Conductor Outside Diameter
7 x Multi-Conductor Assembled Outside Diameter
|
|
Non-Shielded
Cable
Single and Multiple Conductor-All voltages
|
| |
600V |
2kV |
5kV |
8
kV |
| |
| Through
500 kcmil |
3 |
3 |
4 |
6 x Outside
Diameter
|
| |
|
|
|
| |
| 600-1750
kcmil |
4 |
4 |
5 |
7 x Outside
Diameter
|
| |
|
|
|
| |
| 2000
kcmil and above |
5 |
5 |
6 |
8 x Outside
Diameter
|
| |
|
|
|
During
Installation
Cable
should not be pulled with a radius less than that determined for the
installed cable. Due to limitation of side bearing pressure, it is
recommended that larger radius bends be used.
|