POWER CABLES - TYPE MV 105
5kV SHIELDED (SPS) 105°C Rating

CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION
- Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap (Optional Longitudinal Corragated Copper Shield Available)
JACKET
- PVC (Thermosetting Kerite FR Available)

SINGLE CONDUCTOR

  CATALOG NUMBER SUFFIX  
C4400
115 Mil Insulation
CATALOG Size No. O.D.
Over
Jacket Cable
NO. (AWG/ of Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (Inches) (Mils)

(Inches)

(Lbs./Kft)

             
106C05- 6 7 0.47 60 0.69 312
104C05- 4 7 0.52 60 0.74 384
102C05- 2 7 0.58 60 0.80 492
101C05- 1 19 0.62 60 0.84 565
111C05- 1/0 19 0.66 60 0.89 691
121C05- 2/0 19 0.70 80 0.96 801
131C05- 3/0 19 0.75 80 1.01 936
141C05- 4/0 19 0.81 80 1.07 1104
125C05- 250 37 0.86 80 1.13 1257
135C05- 350 37 0.97 80 1.23 1625
150C05- 500 37 1.10 80 1.38 2185
175C05- 750 61 1.29 80 1.57 3077
190C05- 1000 61 1.45 80 1.73 3930
192C05- 1250 91 1.64 110 2.02 5058
195C05- 1500 91 1.76 110 2.14 5917
197C05- 1750 127 1.87 110 2.25 6777
199C05- 2000 127 1.98 110 2.36 7615

†† 140 Mil Insulation for 1250 through 2000 kcmil.

FIVE MINUTE AC FINAL TEST VOLTAGES
Conductor Size  
(AWG / kcmil) AC (kV)
#6 - 1000 23
1250 - 2000 28

CATALOG NUMBER EXAMPLE: 106C05-C4400 = #6 AWG (7) CU 5kV, SPS 115 mil Kerite Extruded Semicon 5 mil CU Tape, 60 mil PVC Jacket.

 

POWER CABLES - TYPE MV 105
5kV SHIELDED (SPS) 105°C Rating
CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap (Optional Longitudinal Corragated Copper Shield Available)
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual Jackets Available)

THREE CONDUCTOR OVERALL PVC JACKET
CATALOG NUMBER SUFFIX 
C4052
115 Mil Insulation
CATALOG Size No. Ground O.D.
Over
Overall Jacket Cable
NO. (AWG/ of Conductor Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft)
               
306C05- 6 7 1 - #6 0.47 80 1.40 1047
304C05- 4 7 1 - #6 0.52 80 1.50 1285
302C05- 2 7 1 - #6 0.58 80 1.63 1649
301C05- 1 19 1 - #4 0.62 80 1.71 1884
311C05- 1/0 19 1 - #4 0.66 110 1.86 2294
321C05- 2/0 19 1 - #4 0.70 110 1.96 2655
331C05- 3/0 19 2 - #6 0.75 110 2.07 3106
341C05- 4/0 19 2 - #6 0.81 110 2.19 3648
325C05- 250 37 2 - #6 0.86 110 2.31 4149
335C05- 350 37 1 - #2 0.97 110 2.53 5340
350C05- 500 37 1 - #1 1.10 140 2.92 7363
375C05- 750 61 1 - #1/0 1.29 140 3.33 10332
390C05- 1000 61 1 - #1/0 1.45 140 3.68 13088

POWER CABLES - TYPE MV 105
5kV SHIELDED (SPS) 105°C Rating
CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap 
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual Jackets Available)

THREE CONDUCTOR OVERALL PVC JACKET GALVANIZED STEEL INTERLOCKED ARMOR (OPTIONAL CONTINOUS CORROGNATED WELDED ALUMINUM ARMOR - CCW AVAILABLE)
 CATALOG NUMBER SUFFIX
C4055
115 Mil Insulation†
CATALOG Size No. Ground O.D.
Over
Overall Jacket Cable
NO. (AWG/ of Conductor Armor Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft)
               
306C05- 6 7 1 - #6 1.48 50 1.59 1438
304C05- 4 7 1 - #6 1.58 50 1.69 1706
302C05- 2 7 1 - #6 1.70 60 1.84 2147
301C05- 1 19 1 - #4 1.79 60 1.92 2408
311C05- 1/0 19 1 - #4 1.87 60 2.00 2896
321C05- 2/0 19 1 - #4 1.97 60 2.10 3291
331C05- 3/0 19 2 - #6 2.08 60 2.21 3781
341C05- 4/0 19 2 - #6 2.20 60 2.33 4367
325C05- 250 37 2 - #6 2.32 60 2.45 4912
335C05- 350 37 1 - #2 2.54 75 2.71 6266
350C05- 500 37 1 - #1 2.86 75 3.03 8232
375C05- 750 61 1 - #1/0 3.27 85 3.46 11408
390C05- 1000 61 1 - #1/0 3.62 85 3.81 14284

 †For diameter over the insulation, refer to Three Conductor PVC Jacket table above.

Note: Underwriters Laboratories additional labeling for cable tray (CT), sunlight and oil resistance is also available as applicable.

 

Home | Index | Terms | www.kerite.com
Copyright © 2000 Kerite. All rights reserved

The Kerite Company
Phone: 203.888.2591 / 800.777.7483
Fax: 203.888.1987

Design by Innovative Systems