POWER CABLE - TYPE MV-105
35kV SHIELDED (SPS) - 105°C Rating

CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap  (Optional Longitudinal Corragated Copper Shield Available)
JACKET
- PVC

SINGLE CONDUCTOR

  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4400 C4400
345 Mil Insulation (100%) 420 Mil Insulation (133%)
CATALOG Size No. O.D. Over Jacket Cable O.D. Over Jacket Cable
NO. (AWG/ of Insul. Thickness O.D. Weight Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                     
111C35- 1/0 19 1.15 80 1.44 1232 1.32 80 1.60 1456
121C35- 2/0 19 1.20 80 1.48 1362 1.36 80 1.65 1592
131C35- 3/0 19 1.25 80 1.53 1518 1.41 80 1.70 1755
141C35- 4/0 19 1.30 80 1.59 1709 1.47 80 1.75 1954
125C35- 250 37 1.36 80 1.64 1884 1.53 110 1.88 2253
135C35- 350 37 1.46 80 1.75 2295 1.63 110 2.01 2733
150C35- 500 37 1.59 110 1.97 3053 1.76 110 2.14 3353
175C35- 750 61 1.80 110 2.18 4055 1.96 110 2.34 4383
190C35- 1000 61 1.95 110 2.33 4986 2.11 110 2.49 5336
192C35- 1250 91 2.09\ 110 2.47 5924 2.26 110 2.64 6293
195C35- 1500 91 2.21 110 2.59 6827 2.38 110 2.76 7213
197C35- 1750 127 2.32 110 2.70 7719 2.49 140 2.94 8303
199C35- 2000 127 2.43 110 2.81 8604 2.59 140 3.04 9209

FIVE MINUTE AC FINAL TEST VOLTAGES
Insulation Level AC (kV)
100% 69
133% 84

CATALOG NUMBER EXAMPLE: 111C35-A4400 = #1/0 AWG (19) CU 35kV, SPS 345 mil Kerite Extruded Semicon, 5 mil CU Tape, 80 mil PVC Jacket.

POWER CABLE - TYPE MV-105
35kV SHIELDED (SPS) - 105°C Rating

CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap 
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual Jackets Available)
THREE CONDUCTOR OVERALL PVC JACKET
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4052 C4052
345 Mil Insulation (100%) 420 Mil Insulation (133%)
CATALOG Size No. Ground O.D. Over Overall Jacket Cable O.D. Over Overall Jacket Cable
NO. (AWG/ of Conductor Insul. Thickness O.D. Weight Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                       
311C35- 1/0 19 1 - #4 1.15 140 3.04 4611 1.32 140 3.39 5474
321C35- 2/0 19 1 - #4 1.20 140 3.13 5052 1.36 140 3.49 5940
331C35- 3/0 19 2 - #6 1.25 140 3.24 5612 1.41 140 3.60 6527
341C35- 4/0 19 2 - #6 1.30 140 3.36 6254 1.47 140 3.72 7199
325C35- 250 37 2 - #6 1.36 140 3.48 6853 1.53 140 3.84 7829
335C35- 350 37 1 - #2 1.46 140 3.71 8264 1.63 140 4.13 9480
350C35- 500 37 1 - #1 1.59 140 4.05 10453 1.76 140 4.41 11570
375C35- 750 61 1 - #1/0 1.80 140 4.50 13813  

POWER CABLE - TYPE MV-105
35kV SHIELDED (SPS) - 105°C Rating

CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap 
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual Jackets Available)

THREE CONDUCTOR GALVANIZED STEEL INTERLOCKED ARMOR WITH
OVERALL
PVC JACKET
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4055 C4055
345 Mil Insulation (100%)† 420 Mil Insulation (133%)†
CATALOG Size No. Ground O.D. Over Overall Jacket Cable O.D. Over Overall Jacket Cable
NO. (AWG/ of Conductor Armor Thickness O.D. Weight Armor Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
 
311C35- 1/0 19 1 - #4 2.98 75 3.15 5551 3.34 85 3.53 6609
321C35- 2/0 19 1 - #4 3.08 75 3.25 6025 3.44 85 3.62 7109
331C35- 3/0 19 2 - #6 3.19 85 3.37 6692 3.55 85 3.73 7735
341C35- 4/0 19 2 - #6 3.31 85 3.50 7377 3.67 85 3.85 8450
325C35- 250 37 2 - #6 3.43 85 3.62 8020 3.79 85 3.98 9124
335C35- 350 37 1 - #2 3.65 85 3.84 9510 4.08 85 4.26 10878
350C35- 500 37 1 - #1 4.00 85 4.18 11822  

†For diameter over the insulation, refer to Three Conductor PVC Jacket table above.

Note: Underwriters Laboratories additional labeling for cable tray (CT), sunlight and oil resistance is also available as applicable.