POWER CABLE - TYPE MV-105
25kV SHIELDED SPS

CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System
INSULATION
- Exclusive Corona-Immune Insulation
INSULATION SHIELD
- Free Stripping Semiconducting Layer
METALLIC SHIELD
- 5 mil Copper Tape, 20% Overlap (Optional Longitudinal Corrugated Copper Shield Available)
JACKET -
PVC (Thermosetting Kerite FR Available)


SINGLE CONDUCTOR

  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4400 C4400 ***
260 Mil Insulation (100%) 320 Mil Insulation (133%)
CATALOG Size No. O.D. Over Jacket  Cable O.D. Over Jacket  Cable
NO. (AWG/ of Insul. Thickness O.D. Weight Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                     
101C25- 1 19 0.93 80 1.19 899 1.06 80 1.32 1049
111C25- 1/0 19 0.97 80 1.23 998 1.10 80 1.38 1176
121C25- 2/0 19 1.01 80 1.27 1121 1.14 80 1.42 1304
131C25- 3/0 19 1.06 80 1.34 1292 1.19 80 1.47 1459
141C25- 4/0 19 1.12 80 1.40 1475 1.25 80 1.53 1649
125C25- 250 37 1.17 80 1.46 1642 1.30 80 1.59 1822
135C25- 350 37 1.28 80 1.56 2038 1.41 80 1.69 2229
150C25- 500 37 1.41 80 1.69 2610 1.54 110 1.89 2933
175C25- 750 61 1.61 110 1.99 3734 1.74 110 2.12 3975
190C25- 1000 61 1.76 110 2.14 4645 1.89 110 2.27 4903
192C25- 1250 91 1.91 110 2.29 5562 2.04 110 2.42 5836
195C25- 1500 91 2.03 110 2.41 6449 2.16 110 2.54 6736
197C25- 1750 127 2.14 110 2.52 7324 2.27 110 2.65 7624
199C25- 2000 127 2.24 110 2.62 8195 2.37 110 2.75 8506

FIVE MINUTE AC FINAL TEST VOLTAGES
Insulation AC
Level (kV)
100% 52
133% 64

CATALOG NUMBER EXAMPLE: 101C25-A4400 = #1 AWG (19) CU 25kV, SPS 260 mil Kerite Extruded Semicon, 5 mil CU Tape, 80 mil PVC Jacket.

Note:Underwriters Laboratories additional labeling for cable tray (CT), sunlight resistance and oil resistance is also available. *** For 133% insulation level, a 345 mil (35kV) thickness must be used.

POWER CABLE - TYPE MV-105
25kV SHIELDED SPS

CONDUCTOR - Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD - Unique Permashield® System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD
- 5 mil Copper Tape, 20% Overlap
(Optional Longitudinal Corragated Copper Shield Available) 
JACKET
- Overall PVC (
Black-STD, Colors Available; Optional individual Jackets Available)

THREE CONDUCTOR OVERALL PVC JACKET
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4052 C4052 ***
260 Mil Insulation (100%) 320 Mil Insulation (133%)
CATALOG Size No. Ground O.D. Over Overall Jacket Cable O.D. Over Overall Jacket Cable
NO. (AWG/ of Conductor Insul. Thickness O.D. Weight Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
301C25- 1 19 1 - #4 0.93 110 2.44 3209 1.06 110 2.72 3767
311C25- 1/0 19 1 - #4 0.97 110 2.53 3540 1.10 110 2.85 4201
321C25- 2/0 19 1 - #4 1.01 110 2.62 3946 1.14 140 3.01 4818
331C25- 3/0 19 2 - #6 1.06\ 110 2.77 4553 1.19 140 3.12 5372
341C25- 4/0 19 2 - #6 1.12 140 2.96 5341 1.25 140 3.24 6007
325C25- 250 37 2 - #6 1.17 140 3.08 5907 1.30 140 3.36 6598
335C25- 350 37 1 - #2 1.28 140 3.31 7260 1.41 140 3.59 7996
350C25- 500 37 1 - #1 1.41 140 3.58 9195 1.54 140 3.86 9987
375C25- 750 61 1 - #1/0 1.61 140 4.09 12604 1.74 140 4.37 13498
390C25- 1000 61 1 - #1/0 1.76 140 4.42 15554        

Note:Underwriters Laboratories additional labeling for cable tray (CT), sunlight resistance and oil resistance is also available. *** For 133% insulation level, a 345 mil (35kV) thickness must be used.

POWER CABLE - TYPE MV-105
25kV SHIELDED SPS

CONDUCTOR - Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD - Unique Permashield® System 
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD
- 5 mil Copper Tape, 20% Overlap 
JACKET
- Overall PVC (
Black-STD, Colors Available;Optional individual Jackets Available)


THREE CONDUCTOR GALVANIZED STEEL INTERLOCKED ARMOR WITH
OVERALL PVC JACKET
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4055 C4055 ***
260 Mil Insulation (100%)† 320 Mil Insulation (133%)†
CATALOG Size No. Ground O.D. Over Overall Jacket Cable O.D. Over Overall Jacket Cable
NO. (AWG/ of Conductor Armor Thickness O.D. Weight Armor Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                       
301C25- 1 19 1 - #4 2.46 75 2.62 4127 2.74 75 2.90 4797
311C25- 1/0 19 1 - #4 2.54 75 2.70 4491 2.86 75 3.03 5282
321C25- 2/0 19 1 - #4 2.64 75 2.80 4936 2.96 75 3.12 5750
331C25- 3/0 19 2 - #6 2.79 75 2.95 5604 3.07 75 3.23 6340
341C25- 4/0 19 2 - #6 2.91 75 3.07 6255 3.19 85 3.37 7086
325C25- 250 37 2 - #6 3.03 75 3.20 6863 3.31 85 3.50 7722
335C25- 350 37 1 - #2 3.25 85 3.44 8363 3.53 85 3.72 9199
350C25- 500 37 1 - #1 3.53 85 3.72 10398 3.81 85 4.00 11290
375C25- 750 61 1 - #1/0 4.04 85 4.23 13990        

†For diameter over the insulation, refer to Three Conductor PVC Jacket table above.

Note:Underwriters Laboratories additional labeling for cable tray (CT), sunlight resistance and oil resistance is also available. *** For 133% insulation level, a 345 mil (35kV) thickness must be used.

 

Home | Index | Terms | www.kerite.com
Copyright © 2000 Kerite. All rights reserved

The Kerite Company
Phone: 203.888.2591 / 800.777.7483
Fax: 203.888.1987