POWER CABLE - TYPE MV-105
15kV SHIELDED (SPS) - 105°
C Rating
CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
METALLIC SHIELD - 5 mil Copper Tape, 20% Overlap (Optional Longitudinal Corrugated Copper Shield Available)
JACKET
- PVC (Thermosetting Kerite FR Available)

SINGLE CONDUCTOR

  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4400 C4400
175 Mil Insulation (100%)†† 220 Mil Insulation (133%)
CATALOG Size No. O.D. Over Jacket Cable O.D. Over Jacket Cable
NO. (AWG/ of Insul. Thickness O.D. Weight Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                     
102C15- 2 7 0.71 80 0.97 636 0.80 80 1.06 725
101C15- 1 19 0.74 80 1.01 713 0.84 80 1.10 805
111C15- 1/0 19 0.78 80 1.05 806 0.88 80 1.14 902
121C15- 2/0 19 0.83 80 1.09 922 0.92 80 1.19 1021
131C15- 3/0 19 0.88 80 1.14 1062 0.97 80 1.24 1166
141C15- 4/0 19 0.93 80 1.20 1236 1.03 80 1.29 1344
125C15- 250 37 0.99 80 1.26 1393 1.09 80 1.37 1528
135C15- 350 37 1.09 80 1.38 1794 1.19 80 1.47 1916
150C15- 500 37 1.22 80 1.51 2346 1.32 80 1.60 2478
175C15- 750 61 1.43 80 1.71 3267 1.52 110 1.87 3533
190C15- 1000 61 1.58 110 1.96 4309 1.67 110 2.05 4479
192C15- 1250 91 1.82 110 2.20 5385 1.82 110 2.20 5385
195C15- 1500 91 1.94 110 2.32 6262 1.94 110 2.32 6262
197C15- 1750 127 2.05 110 2.43 7130 2.05 110 2.43 7130
199C15- 2000 127 2.15 110 2.53 7992 2.15 110 2.53 7992

††220 Mil Insulation for 1250 kcmil and larger.
 

FIVE MINUTE AC FINAL TEST VOLTAGES
Conductor Size  
(AWG/ kcmil) Insulation Level AC (kV)
     
#2-1000 100% 35
1250-2000 100% 44
ALL 133% 44

CATALOG NUMBER EXAMPLE: 102C15-C4400 = #2 AWG (7) CU 15kV, SPS 220 mil Kerite Extruded Semicon, 5 mil CU Tape, 80 mil PVC Jacket.

POWER CABLE - TYPE MV-105
15kV SHIELDED (SPS) - 105°
C Rating
CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer

METALLIC SHIELD
- 5 mil Copper Tape, 20% Overlap (Optional Longitudinal Corragated Copper Shield Available)
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual Jackets Available)

THREE CONDUCTOR OVERALL PVC JACKET

  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4052 C4052
175 Mil Insulation (100%) 220 Mil Insulation (133%)
  O.D.  
CATALOG Size No. Ground O.D. Over Overall Jacket Cable O.D. Over Overall Jacket Cable
NO. (AWG/ of Conductor Insul. Thickness O.D. Weight Insul. Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                       
302C15- 2 7 1 - #6 0.71 110 1.96 2215 0.80 110 2.16 2542
301C15- 1 19 1 - #4 0.74 110 2.04 2516 0.84 110 2.24 2856
311C15- 1/0 19 1 - #4 0.78 110 2.13 2823 0.88 110 2.34 3182
321C15- 2/0 19 1 - #4 0.83 110 2.22 3202 0.92 110 2.43 3576
331C15- 3/0 19 2 - #6 0.88 110 2.34 3701 0.97 110 2.54 4084
341C15- 4/0 19 2 - #6 0.93 110 2.46 4266 1.03 110 2.66 4667
325C15- 250 37 2 - #6 0.99 110 2.58 4787 1.09 110 2.83 5291
335C15- 350 37 1 - #2 1.09 110 2.85 6144 1.19 140 3.12 6794
350C15- 500 37 1 - #1 1.22 140 3.19 8182 1.32 140 3.39 8691
375C15- 750 61 1 - #1/0 1.43 140 3.64 11281 1.52 140 3.84 11856
390C15- 1000 61 1 - #1/0 1.58 140 4.03 14306 1.67 140 4.23 14937

POWER CABLE - TYPE MV-105
15kV SHIELDED (SPS) - 105°
C Rating
CONDUCTOR
- Class "B" Copper Strand (Aluminum Conductors Available) 
CONDUCTOR SHIELD
- Unique Permashield® System
INSULATION - Exclusive Corona-Immune Insulation 
INSULATION SHIELD
- Free Stripping Semiconducting Layer 
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual Jackets Available)

THREE CONDUCTOR GALVANIZED STEEL INTERLOCKED ARMOR WITH
OVERALL PVC JACKET
(OPTIONAL CONTINOUS CORRUGATED WELDED ALUMINUM ARMOR - CCW AVAILABLE)
  CATALOG NUMBER SUFFIX CATALOG NUMBER SUFFIX
A4055 C4055
175 Mil Insulation (100%)† 220 Mil Insulation (133%)†
CATALOG Size No. Ground O.D. Over Overall Jacket Cable O.D. Over Overall Jacket Cable
NO. (AWG/ of Conductor Armor Thickness O.D. Weight Armor Thickness O.D. Weight
PREFIX kcmil) Str. (No.-AWG) (Inches) (Mils) (Inches) (Lbs./Kft) (Inches) (Mils) (Inches) (Lbs./Kft)
                       
302C15- 2 7 1 - #6 1.98 60 2.11 2881 2.18 60 2.31 3284
301C15- 1 19 1 - #4 2.06 60 2.19 3214 2.27 60 2.40 3629
311C15- 1/0 19 1 - #4 2.15 60 2.28 3552 2.35 60 2.48 3979
321C15- 2/0 19 1 - #4 2.24 60 2.38 3967 2.45 75 2.61 4490
331C15- 3/0 19 2 - #6 2.35 75 2.52 4577 2.55 75 2.72 5041
341C15- 4/0 19 2 - #6 2.47 75 2.64 5191 2.67 75 2.84 5672
325C15- 250 37 2 - #6 2.60 75 2.76 5761 2.84 75 3.01 6363
335C15- 350 37 1 - #2 2.86 75 3.03 7224 3.06 75 3.23 7761
350C15- 500 37 1 - #1 3.14 85 3.33 9244 3.34 85 3.53 9826
375C15- 750 61 1 - #1/0 3.58 85 3.77 12503 3.79 85 3.97 13150
390C15- 1000 61 1 - #1/0 3.97 85 4.16 15667 4.17 85 4.36 16370

For diameter over the insulation, refer to Three Conductor PVC Jacket table above.

Note: Underwriters Laboratories additional labeling for cable tray (CT), sunlight and oil resistance is also available as applicable.

 