POWER
CABLE
138kV SHIELDED (SPS) 90°C RATING
CONDUCTOR
- Class B Copper Strand (Aluminum Conductors Available)
CONDUCTOR SHIELD - Unique Permashield® System
INSULATION - Exclusive Corona-Immune EPR Insulation
INSULATION
SHIELD - Thermosetting Semiconduction Layer
METALLIC SHIELD - 5mil Copper Tape, 20% Overlap
JACKET
- PVC (PE Available)
138kV
SINGLE CONDUCTOR
|
|
CATALOG
NUMBER SUFFIX |
|
| 14400
|
| 850
Mils Insulation |
| CATALOG
|
Size
|
No.
|
O.D.
Over |
Jacket
|
Cable
|
| NO.
|
(AWG/
|
of
|
Insul.
|
Thickness
|
O.D.
|
Weight
|
| PREFIX
|
kcmil)
|
Str.
|
(Inches)
|
(Mils)
|
(Inches) |
(Lbs./Kft) |
| |
| 150C98- |
500 |
37 |
2.58 |
140 |
3.03 |
5.42 |
| 175C98- |
750 |
61 |
2.77 |
140 |
3.22 |
6.58 |
| 190C98- |
1000 |
61 |
2.92 |
140 |
3.37 |
7.65 |
| 192C98- |
1250 |
91 |
3.08 |
140 |
3.53 |
8.74 |
| 195C98- |
1500 |
91 |
3.20 |
140 |
3.65 |
9.75 |
| 197C98- |
1750 |
127 |
3.31 |
140 |
3.76 |
10.75 |
| 199C98- |
2000 |
127 |
3.42 |
140 |
3.86 |
11.72 |
| Metallic
shielding may be customized to meet system requirements.
|
THIRTY MINUTE AC FINAL TEST VOLTAGE
| CATALOG
NUMBER EXAMPLE: |
150C98-14400
= 500 kcmil (37) CU, 115kV, SPS 850 mil, Insulation, Extruded
Semicon, 5 mil CU Tape, 110 mil PVC Jacket. |
|