POWER CABLE - KI-600 TYPE
EPR Insulation / CSPE Thermoset Jacket
90°C, 600 Volt, NEC TYPE RHH, RHW-2 or USE-2 - UL Listed
CONSTRUCTION
-Copper Class "B" Conductors per ASTM B-3, B-8 & B-33
-Heat and Moisture Resistant Ethylene Polypropylene Rubber Insulation(EPR)
-Black Heavy Duty Chlorosulfonated Polyethylene Jacket

FEATURES
-Thermoset insulation and jacket provide excellent thermal stability
-Flame Retardant
-Flexible for installation ease

PERFORMANCE STANDARDS
-Insulation in accordance with ICEA S-95-658 Class E-1I & E-2
-Jacket in accordance with ICEA S 95-658 for heavy-duty CSPE
-UL Listed as Types RHH, RHW-2 or USE-2 (size 14AWG not USE-2)
-UL Listed for "CT Use" on sizes 1/0 and larger
-Size 1/0 and larger pass ICEA 70,000BTU and UL 1581 vertical tray flame tests
-Cable pases UL VW-1 vertical flame test
-Rated 90C for normal operation, wet or dry locations, 130C emergency overload conditions, 250C short circuit conditions


SINGLE CONDUCTOR

CATALOG NUMBER SUFFIX 00600
  Insulation Thickness Jacket Nominal OD Approx.
Catalog Prefix Conductor Size (AWG/kcmil) # of Strands Mils (mm) Thickness Mils (Inch) (mm) Net Weight (lbs/K')
114C00- 14 7 30 0.76 15 0.18 4.57 25
112C00- 12 7 30 0.76 15 0.20 5.08 35
110C00- 10 7 30 0.76 15 0.22 5.59 50
                 
108C00- 8 7 45 1.14 15 0.28 7.11 80
106C00- 6 7 45 1.14 30 0.34 8.64 120
104C00- 4 7 45 1.14 30 0.39 9.91 180
102C00- 2 7 45 1.14 30 0.44 11.18 260
                 
101C00- 1 19 55 1.4 45 0.53 13.46 350
111C00- 1/0 19 55 1.4 45 0.57 14.48 425
121C00- 2/0 19 55 1.4 45 0.62 15.75 520
131C00- 3/0 19 55 1.4 45 0.67 17.02 635
141C00- 4/0 19 55 1.4 45 0.72 18.29 780
                 
125C00- 250 37 65 1.65 65 0.83 21.08 955
135C00- 350 37 65 1.65 65 0.94 23.88 1290
150C00- 500 37 65 1.65 65 1.07 27.18 1790
175C00- 750 61 80 2.03 65 1.28 32.51 2640
190C00- 1000 61 80 2.03 65 1.43 36.32 3475


FIVE MINUTE AC FINAL TEST VOLTAGES

Conductor Single Multi††
Size Conductor Conductor
(AWG/ AC AC
kcmil) (kV) (kV)
#6 - #2 9.0 11.5
#1 - #4/0 10.0 14.0
250-500 13.0 16.5
750-1000 14.5 20.0
1250 16.0 -
1500-2000 19.0 -
††Conductor to Conductor

CATALOG NUMBER EXAMPLE: 106C00-00600 = #6 AWG (7) CU 600V, 45 mil Kerite, 30 mil Kerite FR Jacket.