POWER
CABLE - KI-600 TYPE
EPR Insulation / CSPE Thermoset Jacket
90°C, 600 Volt, NEC TYPE RHH, RHW-2 or USE-2 - UL Listed
CONSTRUCTION
-Copper Class "B" Conductors per ASTM B-3, B-8 & B-33
-Heat and Moisture Resistant Ethylene Polypropylene Rubber Insulation(EPR)
-Black Heavy Duty Chlorosulfonated Polyethylene Jacket
FEATURES
-Thermoset insulation and jacket provide excellent thermal stability
-Flame Retardant
-Flexible for installation ease
PERFORMANCE
STANDARDS
-Insulation in accordance with ICEA S-95-658 Class E-1I & E-2
-Jacket in accordance with ICEA S 95-658 for heavy-duty CSPE
-UL Listed as Types RHH, RHW-2 or USE-2 (size 14AWG not USE-2)
-UL Listed for "CT Use" on sizes 1/0 and larger
-Size 1/0 and larger pass ICEA 70,000BTU and UL 1581 vertical tray
flame tests
-Cable pases UL VW-1 vertical flame test
-Rated 90C for normal operation, wet or dry locations, 130C emergency
overload conditions, 250C short circuit conditions
SINGLE
CONDUCTOR
| CATALOG
NUMBER SUFFIX 00600 |
| |
Insulation
Thickness |
Jacket
|
Nominal
OD |
Approx. |
| Catalog
Prefix |
Conductor
Size (AWG/kcmil) |
#
of Strands |
Mils |
(mm) |
Thickness
Mils |
(Inch) |
(mm) |
Net
Weight (lbs/K') |
| 114C00- |
14 |
7 |
30 |
0.76 |
15 |
0.18 |
4.57 |
25 |
| 112C00- |
12 |
7 |
30 |
0.76 |
15 |
0.20 |
5.08 |
35 |
| 110C00- |
10 |
7 |
30 |
0.76 |
15 |
0.22 |
5.59 |
50 |
| |
|
|
|
|
|
|
|
|
| 108C00- |
8 |
7 |
45 |
1.14 |
15 |
0.28 |
7.11 |
80 |
| 106C00- |
6 |
7 |
45 |
1.14 |
30 |
0.34 |
8.64 |
120 |
| 104C00- |
4 |
7 |
45 |
1.14 |
30 |
0.39 |
9.91 |
180 |
| 102C00- |
2 |
7 |
45 |
1.14 |
30 |
0.44 |
11.18 |
260 |
| |
|
|
|
|
|
|
|
|
| 101C00- |
1 |
19 |
55 |
1.4 |
45 |
0.53 |
13.46 |
350 |
| 111C00- |
1/0 |
19 |
55 |
1.4 |
45 |
0.57 |
14.48 |
425 |
| 121C00- |
2/0 |
19 |
55 |
1.4 |
45 |
0.62 |
15.75 |
520 |
| 131C00- |
3/0 |
19 |
55 |
1.4 |
45 |
0.67 |
17.02 |
635 |
| 141C00- |
4/0 |
19 |
55 |
1.4 |
45 |
0.72 |
18.29 |
780 |
| |
|
|
|
|
|
|
|
|
| 125C00- |
250 |
37 |
65 |
1.65 |
65 |
0.83 |
21.08 |
955 |
| 135C00- |
350 |
37 |
65 |
1.65 |
65 |
0.94 |
23.88 |
1290 |
| 150C00- |
500 |
37 |
65 |
1.65 |
65 |
1.07 |
27.18 |
1790 |
| 175C00- |
750 |
61 |
80 |
2.03 |
65 |
1.28 |
32.51 |
2640 |
| 190C00- |
1000 |
61 |
80 |
2.03 |
65 |
1.43 |
36.32 |
3475 |
FIVE MINUTE AC FINAL TEST VOLTAGES
| Conductor |
Single |
Multi†† |
| Size |
Conductor |
Conductor |
| (AWG/ |
AC |
AC |
| kcmil) |
(kV) |
(kV) |
| #6
- #2 |
9.0 |
11.5 |
| #1
- #4/0 |
10.0 |
14.0 |
| 250-500 |
13.0 |
16.5 |
| 750-1000 |
14.5 |
20.0 |
| 1250 |
16.0 |
- |
| 1500-2000 |
19.0 |
- |
| ††Conductor
to Conductor |
CATALOG NUMBER
EXAMPLE: 106C00-00600 = #6 AWG (7) CU 600V, 45 mil Kerite, 30 mil
Kerite FR Jacket.
†For diameter
over the insulation, refer to Three Conductor PVC Jacket table above.
|