POWER
CABLES - TYPE MV-90
5kV NON-SHIELDED (SPS) 90°C Rating
CONDUCTOR
-
Class "B" Copper Strand (Aluminum
Conductors Available)
CONDUCTOR SHIELD - Unique Permashield®
System
INSULATION - Exclusive Corona-Immune
Insulation
JACKET - Thermosetting Kerite FR (CSPE)
SINGLE
CONDUCTOR
CATALOG
NUMBER SUFFIX
30600 (MV90) |
| CATALOG
|
Size
|
No.
|
Insulation
|
O.D.
Over |
Jacket |
Cable
|
| NO.
|
(AWG/
|
of
|
Thickness
|
Insul.
|
Thickness
|
O.D.
|
Weight
|
| PREFIX
|
kcmil)
|
Str.
|
(Mils)
|
(Inches)
|
(Mils)
|
(Inches)
|
(Lbs./Kft)
|
| |
|
|
|
|
|
|
|
| 106C05-
|
6
|
7
|
125
|
0.49
|
80
|
0.67
|
269
|
| 104C05-
|
4
|
7
|
125
|
0.54
|
80
|
0.69
|
339
|
| 102C05-
|
2
|
7
|
125
|
0.60
|
80
|
0.77
|
442
|
| 101C05-
|
1
|
19
|
125
|
0.64
|
80
|
0.81
|
512
|
| 111C05-
|
1/0
|
19
|
125
|
0.68
|
80
|
0.85
|
596
|
| 121C05-
|
2/0
|
19
|
125
|
0.72
|
80
|
0.90
|
702
|
| 131C05-
|
3/0
|
19
|
125
|
0.77
|
95
|
0.98
|
863
|
| 141C05-
|
4/0
|
19
|
125
|
0.83
|
95
|
1.04
|
1026
|
| 125C05-
|
250
|
37
|
140
|
0.92
|
110
|
1.16
|
1240
|
| 135C05-
|
350
|
37
|
140
|
1.02
|
110
|
1.26
|
1606
|
| 150C05-
|
500
|
37
|
140
|
1.15
|
110
|
1.39
|
2141
|
| 175C05-
|
750
|
61
|
155
|
1.37
|
125
|
1.66
|
3122
|
| 190C05-
|
1000
|
61
|
155
|
1.53
|
125
|
1.81
|
3979
|
| 192C05-
|
1250
|
91
|
170
|
1.71
|
140
|
2.01
|
4964
|
| 195C05-
|
1500
|
91
|
170
|
1.83
|
140
|
2.13
|
5818
|
| 197C05-
|
1750
|
127
|
170
|
1.94
|
155
|
2.27
|
6745
|
| 199C05-
|
2000
|
127
|
170
|
2.04
|
155
|
2.38
|
7580
|
FIVE MINUTE AC TEST VOLTAGES
| Conductor
Size |
|
(AWG
/ kcmil) |
AC
(kV) |
| |
#6 - #2/0
|
33
|
| |
#3/0 -
#4/0
|
35
|
|
Single
|
250 -
500
|
39
|
|
Conductor
|
750 -
1000
|
44
|
| |
1250 -
1500
|
48
|
| |
1750 -
2000
|
50
|
| |
|
|
|
Multi
Conductor
|
ALL
|
23
|
|
CATALOG NUMBER
EXAMPLE: |
106C05-30600
= #6 AWG (7) CU 5kV, SPS 125 mil Kerite,
80 mil Kerite FR Jacket. |
Note: Underwriters
Laboratories additional labeling for cable tray (CT) and oil resistance
is also available as applicable.
POWER
CABLES - TYPE MV-90
5kV NON-SHIELDED (SPS) 90°C Rating
CONDUCTOR
-
Class "B" Copper Strand (Aluminum
Conductors Available)
CONDUCTOR SHIELD - Unique Permashield®
System
INSULATION - Exclusive Corona-Immune
Insulation
JACKET - Overall PVC (Black-STD, Colors Available; Optional Individual
Jackets available)
THREE
CONDUCTOR OVERALL PVC JACKET
CATALOG
NUMBER SUFFIX
30052 (MV90)
115 Mil Insulation |
| CATALOG
|
Size
|
No.
|
Ground
|
O.D.
Over |
Overall
Jacket |
Cable
|
| NO.
|
(AWG/
|
of
|
Conductor
|
Insul.
|
Thickness
|
O.D.
|
Weight
|
| PREFIX
|
kcmil)
|
Str.
|
(No.-AWG)
|
(Inches)
|
(Mils)
|
(Inches)
(Lbs./Kft) |
| |
| 306C05-
|
6
|
7
|
1-#6
|
0.47
|
80
|
1.20
|
818
|
| 304C05-
|
4
|
7
|
1-#6
|
0.52
|
80
|
1.30
|
1035
|
| 302C05-
|
2
|
7
|
1-#6
|
0.58
|
80
|
1.43
|
1357
|
| 301C05-
|
1
|
19
|
1-#4
|
0.62
|
80
|
1.51
|
1617
|
| 311C05-
|
1/0
|
19
|
1-#4
|
0.66
|
80
|
1.59
|
1882
|
| 321C05-
|
2/0
|
19
|
1-#4
|
0.70
|
80
|
1.69
|
2212
|
| 331C05-
|
3/0
|
19
|
2-#6
|
0.75
|
110
|
1.86
|
2749
|
| 341C05-
|
4/0
|
19
|
2-#6
|
0.81
|
110
|
1.98
|
3261
|
| 325C05-
|
250
|
37
|
2-#6
|
0.86
|
110
|
2.11
|
3726
|
| 335C05-
|
350
|
37
|
1-#2
|
0.97
|
110
|
2.34
|
4904
|
| 350C05-
|
500
|
37
|
1-#1
|
1.10
|
110
|
2.62
|
6612
|
| 375C05-
|
750
|
61
|
1-#1/10
|
1.29
|
140
|
3.13
|
9639
|
| 390C05-
|
1000
|
61
|
1-#1/10
|
1.45
|
140
|
3.45
|
12328
|
POWER
CABLES - TYPE MV-90
5kV NON-SHIELDED (SPS) 90°C Rating
CONDUCTOR
-
Class "B" Copper Strand (Aluminum
Conductors Available)
CONDUCTOR SHIELD - Unique Permashield® System
INSULATION - Exclusive Corona-Immune Insulation
JACKET
- Overall PVC (Black-STD, Colors Available; Optional Individual
Jackets available)
THREE CONDUCTOR GALVANIZED STEEL INTERLOCKED ARMOR WITH
OVERALL PVC JACKET
(OPTIONAL CONTINOUS CORROGNATED WELDED ALUMINUM ARMOR
- CCW AVAILABLE)
CATALOG
NUMBER SUFFIX
30055 (MV90)
115 Mil Insulation† |
| CATALOG
|
Size
|
No.
|
Ground
|
O.D.
Over |
Overall
Jacket |
Cable
|
| NO.
|
(AWG/
|
of
|
Conductor
|
Armor
|
Thickness
|
O.D.
|
Weight
|
| PREFIX
|
kcmil)
|
Str.
|
(No.-AWG)
|
(Inches)
|
(Mils)
|
(Inches)
|
(Lbs./Kft) |
| |
| 306C05-
|
6
|
7
|
1-#6
|
1.29
|
50
|
1.40
|
1195
|
| 304C05-
|
4
|
7
|
1-#6
|
1.39
|
50
|
1.50
|
1446
|
| 302C05-
|
2
|
7
|
1-#6
|
1.51
|
50
|
1.62
|
1811
|
| 301C05-
|
1
|
19
|
1-#4
|
1.60
|
60
|
1.73
|
2135
|
| 311C05-
|
1/0
|
19
|
1-#4
|
1.68
|
60
|
1.81
|
2430
|
| 321C05-
|
2/0
|
19
|
1-#4
|
1.78
|
60
|
1.91
|
2951
|
| 331C05-
|
3/0
|
19
|
2-#6
|
1.89
|
60
|
2.02
|
3439
|
| 341C05-
|
4/0
|
19
|
2-#6
|
2.01
|
60
|
2.14
|
3999
|
| 325C05-
|
250
|
37
|
2-#6
|
2.13
|
60
|
2.26
|
4514
|
| 335C05-
|
350
|
37
|
1-#2
|
2.35
|
75
|
2.52
|
5854
|
| 350C05-
|
500
|
37
|
1-#1
|
2.63
|
75
|
2.79
|
7682
|
| 375C05-
|
750
|
61
|
1-#1/0
|
3.08
|
75
|
3.24
|
10735
|
| 390C05-
|
1000
|
61
|
1-#1/0
|
3.40
|
85
|
3.59
|
13622
|
†For diameter
over the insulation, refer to Three Conductor PVC Jacket table above.
Note: Underwriters
Laboratories additional labeling for cable tray (CT), sunlight and